InstallationInstructionsforElectricBoilers (CANADA)December 2011VERSION 11THERMOLEC
Page 810.3 Simulate a heating demand by setting the thermostat higher than the room temperature.10.4 Switch the mode selector to position and ch
Page 914 WarrantyThermolec Ltd. warrants against defects in materials and workmanship the heat generator casing of its boiler and the heating elements
Electric Boiler Warranty Registration FormName : _______________________________________________________________________________Address : ____________
Page 13Volts / TotalHeight Phases KWWatts Ohms Part # Watts Ohms Part # Watts Ohms Part # Watts Ohms Part #3.003.006.009.0011.003000 19.2 CBLR0653000
Page 14Volts / Total V noitarugifnoC#/ tloHeight Phases KWelement élém. Watts Ohms Part #13" Cyl. 18.00 6 3000 14.4 CBLR05124.00 6 4000 10.8 CBLR
TEMPERATURE / TEMPÉRATUREPRESSURE / PRESSIONSUPPLY TORADIATORSAIRPURGERBLEEDING VALVESAFETY VALVEROOM THERMOSTATWATER FEEDPRESSUREREDUCING VALVETEMPER
TEMPERATURE / TEMPÉRATUREPRESSURE / PRESSIONAIRPURGERBLEEDING VALVESHUT-OFFVALVEELECTRICBOILERTEMPERATURE /PRESSURE GAUGESUPPLY TORADIATORSRETURN FROM
TEMPERATURE / TEMPÉRATUREPRESSURE / PRESSIONACBAIR PURGERBLEEDINGVALVEMAINTENANCEVALVESUPPLY TORADIATORSEXPANSIONTANKMOTORIZEDVALVEA-B PORTNORMALLY OP
Page 1Installation Guidelines for Thermolec Electric Boilers Model B1 Important1.1 These instructions should be used as a general guide only. Electri
Page 24 Components Note : The model shown here is a typical Dual-Energy boiler 23kW / 240 Volts / 1phase.5 Standard specifications for all modelsTabl
Page 3Please use Table 3 below to select the wire size for the power supply. (It is not mandatory to use copper wire).Wire Size 12 10 864321000000Amps
Page 46.2 In order to ensure an adequate flow rate :6.21 Pressure loss (referred as "Head") caused by water friction in the system should
Page 56.4 The automatic pressure relief valve supplied with the boiler is required to prevent dangerous pressure build-ups in the system in case of s
Page 6Electronic AquastatFig. 4 Fig. 58.7 The outdoor sensor will :a) Maintain the selected maximum water temperature when the outdoor temperature
Page 79.8 Set the thermostat above the room temperature. The system should start.9.9 Make sure the pump starts running as soon as the system starts.